7-5
Alarm Configuration
LineInputA: Defines the Load Shedding actions that will be executed when an
Over Current Branch Alarm is triggered at Line Input "A".
LineInputB: Defines the Load Shedding actions that will be executed when an
Over Current Branch Alarm is triggered at Line Input "B".
FuseA1-A4: Defines the Load Shedding actions that will be executed when an
Over Current Branch Alarm is triggered at Fuses A1 through A4.
FuseB1-B4: Defines the Load Shedding actions that will be executed when an
Over Current Branch Alarm is triggered at Fuses B1 through B4.
After selecting the branch or line, use the following parameters to configure Load
Shedding functions for the desired branch or line.
Enable: Enables/Disables Load Shedding for the corresponding alarm. When
enabled, the VMR will switch the user specified plugs whenever current load
exceeds the Alarm Set Threshold value. (Default = Disable.)
PlugState: Determines whether the selected plugs/plug groups will be switched
On or Off when Load Shedding is enabled and current load exceeds the user-
defined Alarm Set Threshold. For example, if the Plug State is "Off", then plugs
or plug groups will be switched Off when the Alarm Set Threshold is exceeded.
(Default = Off.)
AutoRecovery: Enables/Disables the Auto Recovery feature for the selected
branch or line. When both Load Shedding and Auto Recovery are enabled, the
VMR will return plugs to their former On/Off state after current load falls below the
Alarm Clear Threshold value. This allows the VMR to "undo" the effects of Load
Shedding after current load has returned to an acceptable level. (Default = Off.)
PlugAccess: Determines which Plug(s) will be switched when current load
exceeds the Alarm Set Threshold and Load Shedding is triggered. For example,
if plugs A1, A2 and A3 are selected, then these plugs will be switched On or Off
whenever current load exceeds the Alarm Set Threshold. (Default = undefined.)
PlugGroupAccess: Determines which Plug Group(s) will be switched when the
Load Shedding feature is triggered. For example, if you have defined a Plug Group
named "test", which includes Plugs B3, B4 and B5, and then selected the "test" Plug
Group via the Plug Group Access parameter, then all of the plugs in the "test" Plug
Group will be switched On or Off whenever the current load exceeds the Alarm Set
Threshold. (Default = undefined.)
Note: Plug Groups must first be defined (as described in Section 5.6) before
they will be displayed in the Load Shedding menu's Plug Group Access
submenu.
After setting parameters for a given branch or line, you may also define additional
parameters for other branches or lines (if present.) To set Load Shedding parameters
for other branches or lines, return to the Alarm Configuration menu and then repeat the
procedure described in Section 7.1.1.